MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Must provide an up to date fire extinguisher in machine room
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.8 Switch Keys
|
|
|
With the major upgrade of elevator #2, the fireman’s service phase I key switch was changed to meet the A17.1 2016 code. This code requires a different key than the other existing elevators in the Louderman complex. The current adopted codes of the authority having jurisdiction require that all fireman’s service keys for elevators in a building are required to be keyed the same. Change the fireman’s service key of this elevator to the “FEOK1” key as elevator #2.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
To complete the annual portion of the test, must complete fire service, and emergency light, bell, phone
|
8/17/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, buffers compressed and emergency light/bell tested before the inspection is completed.
|
6/23/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
5 year test must be done. Could not locate a 5 year test tag.
|
8/17/2023
|
A17.1-1996 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
1001.2(c)(13)
|
x
|
|
The counterweight retaining rod shall have two nuts fastened together against the counterweight frame with a cotter pin through each securing rod end.
|
6/23/2023
|