Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x 5 year test must be done. Could not locate a 5 year test tag. 8/17/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x To complete the annual portion of the test, must complete fire service, and emergency light, bell, phone 8/17/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The weight test shall be performed, safeties set, buffers compressed and emergency light/bell tested before the inspection is completed. 6/23/2023
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 1001.2(c)(13) x The counterweight retaining rod shall have two nuts fastened together against the counterweight frame with a cotter pin through each securing rod end. 6/23/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Must provide an up to date fire extinguisher in machine room
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys With the major upgrade of elevator #2, the fireman’s service phase I key switch was changed to meet the A17.1 2016 code. This code requires a different key than the other existing elevators in the Louderman complex. The current adopted codes of the authority having jurisdiction require that all fireman’s service keys for elevators in a building are required to be keyed the same. Change the fireman’s service key of this elevator to the “FEOK1” key as elevator #2.