Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In car emergency telephone shall work. 4/8/2019
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Car door restrictor shall work. 4/8/2019
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 1002.3f x 8.4.10.12(c) - Make repairs or adjustments to the counterweight derailment assembly in the pit. The counterweight hits the counterweight derailment assembly when counterweight buffer is compressed. 4/8/2019
A17.1-1996 : Elevators 1.3 - Operating control devices 1001.2(a)(3) Replace the jewel in the car station to its normal position. 7/22/2019
A17.1-1996 : Elevators 2.18 - Traction drive machines 1001.2(b)(16) x Repair hoist machine leaks. 6/23/2020
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The machine room floor shall be kept clean. 7/27/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean. 7/27/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A monthly fire service testing log shall be completed and kept on-site. 7/27/2020
A17.1-1996 : Elevators 3.20 - Governor rope 1001.2(c)(26) x x The governor rope is damaged and shall be replaced. Determine and correct cause of damage. - Elevator Red Tagged 6/23/2020
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The machine room floor shall be kept clean. 7/27/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean. 7/27/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A monthly fire service testing log shall be completed and kept on-site. 7/27/2020
A17.1-1996 : Elevators 2.18 - Traction drive machines 1001.2(b)(16) x Repair hoist machine leaks. 6/30/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 The pit shall be kept clean. Clean the pit. 2/2/2023
conversion conversion conversion - reinspect x Emergency phone not working 1/24/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean the car top. The car top shall be kept clean. 7/27/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Governor rope has been replaced. While unloading weights to test the new governor rope, an unsafe and dangerous situation was created by a tenet in the building. The elevator was locked out of service and testing will be re-scheduled for a later date. Full testing of governor rope still required. 6/30/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x All category 5 testing items still need to be performed and witnessed. 6/23/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean the car top. The car top shall be kept clean. 7/27/2020