MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean the car top. The car top shall be kept clean.
|
7/27/2020
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
The machine room floor shall be kept clean.
|
7/27/2020
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
The pit shall be kept clean.
|
7/27/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
A monthly fire service testing log shall be completed and kept on-site.
|
7/27/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean the car top. The car top shall be kept clean.
|
7/27/2020
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
The machine room floor shall be kept clean.
|
7/27/2020
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
The pit shall be kept clean.
|
7/27/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
A monthly fire service testing log shall be completed and kept on-site.
|
7/27/2020
|
A17.1-1996 : Elevators
|
1.3 - Operating control devices
|
1001.2(a)(3)
|
|
|
Replace the jewel in the car station to its normal position.
|
7/22/2019
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
The pit shall be kept clean. Clean the pit.
|
2/2/2023
|
A17.1-1996 : Elevators
|
2.18 - Traction drive machines
|
1001.2(b)(16)
|
x
|
|
Repair hoist machine leaks.
|
6/23/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Governor rope has been replaced. While unloading weights to test the new governor rope, an unsafe and dangerous situation was created by a tenet in the building. The elevator was locked out of service and testing will be re-scheduled for a later date. Full testing of governor rope still required.
|
6/30/2020
|
A17.1-1996 : Elevators
|
3.20 - Governor rope
|
1001.2(c)(26)
|
x
|
x
|
The governor rope is damaged and shall be replaced. Determine and correct cause of damage. - Elevator Red Tagged
|
6/23/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
All category 5 testing items still need to be performed and witnessed.
|
6/23/2020
|
A17.1-1996 : Elevators
|
2.18 - Traction drive machines
|
1001.2(b)(16)
|
x
|
|
Repair hoist machine leaks.
|
6/30/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency phone not working
|
1/24/2019
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency telephone shall work.
|
4/8/2019
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
Car door restrictor shall work.
|
4/8/2019
|
A17.1-1996 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
1002.3f
|
x
|
|
8.4.10.12(c) - Make repairs or adjustments to the counterweight derailment assembly in the pit. The counterweight hits the counterweight derailment assembly when counterweight buffer is compressed.
|
4/8/2019
|