Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No In the machine room at the top of the hoistway, there is a small open section that creates a potential falling hazard. This open area shall be covered with approved material. 5/24/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The cover for the hoistway access release chain is missing at the top floor landing. This cover shall be installed to prevent unpermitted access to the hoistway. 5/24/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The drive sheave isolation pads are excessively worn and some are missing. The isolation pads shall be replaced. 9/16/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Brake drum coupling needs a cotter pin or a jamb nut installed. 7/1/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/1/2025
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No The machine room shall be cleaned. 7/1/2025