Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No A minimum of 10 fc of lighting is required in the overhead machine room.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 No No Each passenger car shall be fully enclosed. The open sections on the side and top of the car shall be covered with approved material.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 No No Each passenger car shall be fully enclosed. The open sections on the side and top of the car shall be covered with approved material. Cited multiple years.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency alarm bell is not working. 11/3/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Obtain and display a current state operating certificate.
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Provide a permanent ladder or stairway to overhead machine room.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The car platform toe guard shall be re-attached. 9/16/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The in car emergency alarm bell shall be operational. 9/16/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The overhead machine room door shall be self-locking and self-closing.
conversion conversion conversion - reinspect Yes No Alarm bell shall work. 11/27/2019
conversion conversion conversion - reinspect Yes No Basement and overhead machine rooms shall have self closing and self locking doors. 11/27/2019
conversion conversion conversion - reinspect Yes No Car lights shall be guarded. 11/27/2019
conversion conversion conversion - reinspect Yes No Enclose hall push button wiring at floors B, 2, and 3. 11/27/2019
conversion conversion conversion - reinspect Yes No Guard or eliminate liquid carrying pipes in machine room. 11/27/2019
conversion conversion conversion - reinspect Yes No Hoist cables shall be re-socketed every 24 months. 11/27/2019
conversion conversion conversion - reinspect Yes No Hoistway shall be enclosed. 11/27/2019
conversion conversion conversion - reinspect Yes No In car stop switch shall be labeled. 11/27/2019
conversion conversion conversion - reinspect Yes No Install floor in overhead machine room. 11/27/2019
conversion conversion conversion - reinspect Yes No Lighting is required in overhead machine room to produce 10 ftc in all areas of the room. 11/27/2019
conversion conversion conversion - reinspect Yes No Obtain and display a current state operating certificate. 11/27/2019
conversion conversion conversion - reinspect Yes No Provide hoistway access means at top and bottom floors. 11/27/2019
conversion conversion conversion - reinspect Yes No Provide machine room fire extinguisher. 11/27/2019
conversion conversion conversion - reinspect Yes No Provide permanent stairs or ladder to overhead machine room. 11/27/2019