Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door is not self-locking. 4/16/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall be made operational. Re-inspection required
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No OSV is not sealed. Perform test on or before next annual inspection. 3/5/2021
A17.1-1996 : Elevators 2.37 - Pressure Switch 1004.2(b)(20) No No The hydraulic pressure switch on the elevator controller would bot activate when the oil pressure was decreased. The pressure switch shall be repaired to operate as required. 6/18/2019