Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 2.37 - Pressure Switch | 1004.2(b)(20) | The hydraulic pressure switch on the elevator controller would bot activate when the oil pressure was decreased. The pressure switch shall be repaired to operate as required. | 6/18/2019 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | OSV is not sealed. Perform test on or before next annual inspection. | 3/5/2021 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Machine room door is not self-locking. | 4/16/2024 |