Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (D) - Brakes (D)2 x x Car running through brake at second landing to the poiint door could not be opened. Adjust/repair brake for proper operation. This is not a red tag item 11/22/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The elevator telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. 12/23/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 12/23/2019
MO Minimum : Elevators (R) - Power Operated Special Purpose Elevators (R)6 Repair, 1st & 2nd roof top landing door closed/door locked contact switches. 5/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Car call button shall be so marked "Emergency Use Only" on landing and car side of door. 5/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide MCP 9/23/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state elevator certificate 9/23/2021