MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/29/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Car emergency telephone needs to be programmed to the current elevator contractor.
|
6/1/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work, phone doesn't respond when button is pushed. Re-inspection required
|
10/21/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work. Has ring tone but no answer. Repair or replace
|
3/31/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone line does not work.
|
4/29/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher in machine room is expired.
|
10/21/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Holes in the hoistway need to covered and fireproofed
|
10/21/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door needs to be self locking & self closing.
|
10/21/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light does not work
|
10/21/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
|
|
Pit light does not work.
|
10/21/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
10/21/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The alarm bell shall be operational on auxiliary power.
|
8/12/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
The fire extinguisher in the machine room is expired.
|
3/29/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher is expired, needs replaced or serviced.
|
10/21/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The in car emergency light shall be operational
|
8/12/2020
|
A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
8.11.2.1.3(b)
|
|
|
The light on the top of the car shall be operational.
|
3/29/2019
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
n/a
|
|
|
The machine room fire extinguisher shall have a current test tag.
|
3/29/2019
|
A17.1-2016 : Elevators
|
1.13 - Emergency exit
|
2.14.1.10
|
x
|
x
|
The side emergency exits shall be permanently fixed in the closed position. (The cab has been altered, possibly in 2015 when the car was modernized. Access to the side emergency exits are now blocked)
|
8/12/2020
|