Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements The machine room shall contain an ABC type fire extinguisher with a current date certification. 3/29/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/29/2020
A17.1-2016 : Elevators 2.7 - Fire Extinguisher n/a The machine room fire extinguisher shall have a current test tag. 3/29/2020
A17.1-2016 : Elevators 3.2 - Car top light and outlet 8.11.2.1.3(b) The light on the top of the car shall be operational. 3/29/2020
A17.1-2016 : Elevators 1.13 - Emergency exit 2.14.1.10 x x The side emergency exits shall be permanently fixed in the closed position. (The cab has been altered, possibly in 2015 when the car was modernized. Access to the side emergency exits are now blocked) 8/12/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 4/29/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Re-inspection required 5/31/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door needs to be self locking & self closing 10/21/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher is expired. Needs to be serviced or replaced 10/21/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Pit light does not work. 10/21/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 10/21/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit lights do not work 10/21/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Fire extinguisher is expired. 10/21/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. Has a ring tone but no answer. Repair or replace 3/31/2023