A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
In car stop switch is not overridden when car is in flight on phase I fire recall, needs repaired. Re-inspection required
|
6/20/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key.
|
6/12/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed.
|
6/12/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety.
|
11/6/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. Testing was suspended after Elevator #1 was red tagged. Only the elevator hoistway and pit were inspected. Reinspection required.
|
1/30/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Repair inoperable door restrictor.
|
3/8/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Install crosshead data tag.
|
4/6/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety code concern. Without motion the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch
|
4/6/2023
|