Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)2 Alterations x Fire sprinklers and heat detectors have been added to the elevator hoistway and machine room. Shunt trip disconnects shall be added and electrically tied into the heat detectors to remove power from the elevator before the application of water. Reinspection and testing will be required. 5/20/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Repair inoperative door restrictor. 2/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x The car “door open” button would not open the elevator car door. Repair or replace car door open button. 12/17/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. 11/6/2019
MO Minimum : Elevators (H) - Machine Rooms (H)4 The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. 4/6/2023
MO Minimum : Elevators (H) - Machine Rooms (H)1 The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. 4/6/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. 4/6/2023
MO Minimum : Elevators (S) - Fire Service (S)1 x x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The car doors will not open on phase II operation. Elevator was red tagged and placed out of service. Reinspection is required. 12/17/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:Phase I did not initiate when the fireman's emergency service key was turned to the “ON” position. The elevator was placed out of service. No further testing was performed, a full reinspection will be required. 5/20/2019
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting has been changed to a motion type switch to activate. While this is an energy saving measure, it also is a safety code concern. Without motion the switch deactivates the lighting, thereby leaving maintenance personnel with no lighting. Remove motion type switch to a conventional on/off switch 4/6/2023