MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
|
A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
8.11.2.1.3(b)
|
|
|
The car top lighting pendant station shall be repaired or replaced. Note: The cord is bad where it connects to the pendant and could be an electrical shock hazard.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State Operating Certificate is missing from the machine room.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Provide working audible indicator inside car on Phase 1 recall.
|
9/19/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The in car emergency lighting and alarm bell shall be operational.
|
3/30/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post the current state operating certificate.
|
8/25/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The car top light shall be operational.
|
8/25/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned
|
8/25/2020
|
MO Minimum : Elevators
|
(J) - Counterweights
|
(J)1
|
|
|
The counterweight Rollers need to be replaced, the Counterweight frame is real loose
|
8/25/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)10 Car Floors
|
|
|
Car sills need to be cleaned out
|
8/25/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The Hoistway needs to be cleaned
|
8/25/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
8/25/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Provide 2 working lights on emergency lighting.
|
8/25/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Clean the car top.
|
8/25/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Car top light shall work.
|
8/25/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean the car top.
|
8/25/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
4/29/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
The means to restrict opening of the car door shall be operational.
|
3/7/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The in car emergency lights shall be operational.
|
3/7/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car alarm bell shall be operational on main and auxiliary power.
|
3/7/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Governor rope pull out/thru and governor switch/jaw portion of the category 5 testing still needs to be completed.
|
3/10/2023
|