Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Door closing shall be constant pressure operation on Phase 2 fire service. 9/21/2018
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes Complete category 5 inspection items that still remain (Slide, car & CW buffer, & 125% brake test). 9/21/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display current state operating certificate. 4/29/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light shall work. 4/29/2021
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. Clean the pit. 4/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No 8.6.4.7.1 - The hoistway shall be kept clean of dirt and rubbish. Clean the hoistway. 4/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No The car top shall be cleaned. 4/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No The top and bottom counterweight rollers are worn and require replacement. 4/29/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO state operating certificate shall be posted in the elevator machine room. 4/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 4/29/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. 10/23/2023
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. Clean the pit. 10/23/2023