MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
MCP needed
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Lighting in the machine room shall be not less than ten (10) foot-candles at floor level.
|
12/7/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door lock broken. Must be self-locking
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Phase 1 signage missing
|
12/7/2023
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
Scavenger pump in pit pumps oil back to hydraulic tank in machine room. Remove scavenger pump
|
12/7/2023
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
Scavenger pump in pit pumps oil back to hydraulic tank in machine room. Remove scavenger pump
|
12/7/2023
|