Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Scavenger pump in pit pumps oil back to hydraulic tank in machine room. Remove scavenger pump 12/7/2023
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Scavenger pump in pit pumps oil back to hydraulic tank in machine room. Remove scavenger pump 12/7/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emg phone was not working
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 need phase one fire serv. bezel replaced not readable
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Phase 1 signage missing 12/7/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in the machine room shall be not less than ten (10) foot-candles at floor level. 12/7/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door lock broken. Must be self-locking
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) MCP needed