Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door lock broken. Must be self-locking 5/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No mach room door lock needs to be undeafeatable self locking 5/15/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Lighting in the machine room shall be not less than ten (10) foot-candles at floor level. 12/7/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Phase 1 signage missing 12/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No MCP needed 5/15/2026
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 No No need phase one fire serv. bezel replaced not readable 5/15/2026
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No emg phone was not working 5/15/2026
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 No No Scavenger pump in pit pumps oil back to hydraulic tank in machine room. Remove scavenger pump 12/7/2023
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 No No Scavenger pump in pit pumps oil back to hydraulic tank in machine room. Remove scavenger pump 12/7/2023