MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean pit.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Hold position does not work on phase 2 fire service
|
8/7/2018
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)3
|
x
|
|
Machine room run switch (up and down) shall return to the neutral position.
|
10/5/2020
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Diameter loss due to rouging exceeds proposed criteria
|
10/5/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
x
|
|
Fireman's recall needs to be tested.
|
10/5/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test counterweight buffer at rated speed. Re-inspection required
|
10/19/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test car buffer, rated load & speed. Re-inspection required
|
10/19/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test car safeties, rated load & speed. Re-inspection required
|
10/19/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test machine brake with 125% rated load. Re-inspection required
|
10/19/2022
|