Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean.
MO Minimum : Elevators (I) - Pits (I)1 Clean pit.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test counterweight buffer at rated speed. Re-inspection required 10/19/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test car buffer, rated load & speed. Re-inspection required 10/19/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test car safeties, rated load & speed. Re-inspection required 10/19/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test machine brake with 125% rated load. Re-inspection required 10/19/2022
MO Minimum : Elevators (F) - Electrical Switches (F)3 x Machine room run switch (up and down) shall return to the neutral position. 10/5/2020
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Diameter loss due to rouging exceeds proposed criteria 10/5/2020
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage x Fireman's recall needs to be tested. 10/5/2020
conversion conversion conversion - reinspect x Hold position does not work on phase 2 fire service 8/7/2018