Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (I) - Pits (I)1 Clean pit. 10/10/2020
MO Minimum : Elevators (I) - Pits (I)1 Clean pit. 10/10/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Elevator car door restrictor does not work, needs repaired. Re-inspection required
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)9 Capacity Plate Need to replace missing capacity plate in car 9/15/2023
MO Minimum : Elevators (I) - Pits (I)1 Pit has standing water, need to remove water and repair sump pump 10/15/2024
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Replace missing phase I and II fire service operating instructions signs.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test counterweight buffer at rated speed. Re-inspection required 10/19/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x When the elevator is on phase II fire service at the alternate landing, it will not revert back to phase I fire recall when the in car phase II fire service switch is turned to off. Needs repaired, Re-inspection required