Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No Replace missing hoistway door safety retainers on 6th & 7th floor hoistway doors 7/23/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Need to repair the COP panel so that it is secure and closes the gap between the COP panel and car door
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal No No Audible fire hat signal does not sound on phase I
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Replace missing phase I fire service operating instructions sign 7/23/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 7/23/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Traveling cable insulation jacket is damaged. Repair or replace traveling cable 8/31/2017
conversion conversion conversion - reinspect Yes No Repair car door restrictor 8/6/2018
conversion conversion n/a No No sight guard missing on 2nd floor and missing part of it on fist floor 8/31/2017
conversion conversion n/a No No Machine room lights 8/31/2017