Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 Elevator controller is in machine room, accessible to general public. Provide a locked enclosure and controller meeting clearance requirements of NEC or apply for variance. 1/7/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Provide 10 foot candle lighting in machine room. 1/7/2020
MO Minimum : Elevators (A) - Hoistways (A)5 Bottom landing hoistway door blocked by trash. Rule 4.2 1/7/2020
MO Minimum : Elevators (A) - Hoistways (A)5 Hoistway door gibbs missing on top and 1st floor doors. Rule 4.2 1/7/2020
MO Minimum : Elevators (A) - Hoistways (A)16 Close open electric boxes on car top. Rule 3.12 1/7/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lights need to be 10 ft candles in front of Controller. Presently 3 ft candles. 1/7/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate in machine room. 1/7/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2 way communication is not working. Re-inspection required 5/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide current year tested fire extinguisher in the elevator machine room.
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post Phase I instructions near the f/f switch in the lobby.
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Post Phase II instructions inside car.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Phone works, provide means for operators to identify location.