MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Close open electric boxes on car top. Rule 3.12
|
1/7/2020
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)5
|
|
|
Bottom landing hoistway door blocked by trash. Rule 4.2
|
1/7/2020
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)5
|
|
|
Hoistway door gibbs missing on top and 1st floor doors. Rule 4.2
|
1/7/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2 way communication is not working. Re-inspection required
|
5/19/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Phone works, provide means for operators to identify location.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Elevator controller is in machine room, accessible to general public. Provide a locked enclosure and controller meeting clearance requirements of NEC or apply for variance.
|
1/7/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Provide 10 foot candle lighting in machine room.
|
1/7/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lights need to be 10 ft candles in front of Controller. Presently 3 ft candles.
|
1/7/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post Phase I instructions near the f/f switch in the lobby.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post Phase II instructions inside car.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current operating certificate in machine room.
|
1/7/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Provide current year tested fire extinguisher in the elevator machine room.
|
|