A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Repair the emergency phone.
|
12/12/2022
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone working, but not identifying location.
|
7/31/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
No
|
No
|
The fire service, phase 1, key switch bezel is broken, Replace.
|
9/29/2022
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.8 Switch Keys
|
No
|
No
|
Phase I recall key is different than the Phase II key on COP. Re-key both to FEOK1
|
9/5/2023
|