Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light needs repaired and 4X4 wiring boxes(covers installed) 1/14/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 machine room door needs to kept closed 1/14/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) 2019): I-6 needs covers on electrical boxes in pit and pit light repaired (2020): I(6)/A(16): Replace 4x4 box covers in pit. 1/14/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) 2019-2020: I(6): Pit 120v receptacle shall be function independent of pit light switch. (Switch currently controls light and receptacle) 1/14/2022
MO Minimum : Elevators (I) - Pits (I)1 2018-2020: I(1): Pit needs to be cleaned of all oil and trash.( excessive Oil from leaking packing and facility debris). REINSPECTION WITHIN 30 days Due to multiple violation write-ups without repairs. 1/14/2022
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 2018-2020: O(4): Cylinder packing must be replaced. Scavenger pump shall be removed. REINSPECTION WITHIN 30 days. 1/14/2022
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal S(1): Fire hat illumination shall work as designed. 8/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements G(1): Hall “in-use” indicators shall work as designed. 1/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements G(1): Hall “in-use” indicators shall work as designed. 12/24/2020
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal S(1): Fire hat illumination shall work as designed. 12/24/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 machine room door needs to kept closed 7/25/2019 12/24/2020
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light needs repaired and 4X4 wiring boxes(covers installed) 8/25/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Scavenger pump shall be removed 1/14/2022
conversion conversion n/a pit needs to be cleaned of all oil and trash 12/24/2020
conversion conversion n/a Jack needs to be repacked--seal replaced 12/24/2020
MO Minimum : Elevators (A) - Hoistways (A)16 Reinstall missing electrical box cover on gate bump edge. 6/8/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate 11 CSR 40-5.100(2) : Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. (Mounted to wall preferred) 2006 posted 6/8/2023
MO Minimum : Elevators (I) - Pits (I)1 Remove dirt and rubbish from pit floor 7/2/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Provide operational reopening device 8/9/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Provide operational telephone in cab 6/1/2023
conversion conversion conversion - reinspect x Phase I & phase II key switch needs replaced--second notice 7/25/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x (G)1 - 8.6.4.15/1.6.1/8.11.2.1.1(f)/8.6.4.15 : 2-way communication device shall give proper location message, (REINSPECTION REQUIRED 12/6/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x I(1) Pit scavenger pump will be removed. (REINSPECTION TO ENFORCE, NOTED MULTIPLE YEARS) 10/27/21& 12/6/21 - No change in status. 1/14/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. x Pit has approx 1” of oil in pit. Repack jack and/or repair leak. REINSPECTION TO ENFORCE. (Has been written up multiple times) 11/21/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x (G)1 - 8.6.4.15/1.6.1/8.11.2.1.1(f)/8.6.4.15 : 2-way communication device shall give proper location message, (REINSPECTION REQUIRED) 12/6/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x B(11) / 1004.2(a)(6): 2-way communication shall work. (No answer). REINSPECTION WITHIN 30 days 12/24/2020