Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Elevator has an OSV in the pit that was due for inspection in 2023, there is no data tag to show when it was last inspected.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Elevator has OSV in the pit that was due for an inspection in 2023, there is no data tag to show when it was last inspected
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher out of date 10/6/2022
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Non elevator related storage shall not be kept in elevator equipment room 7/12/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x OSV failed and needs to be replaced, unable to complete test. Re-inspection required