Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x Telephone will not call out 7/25/2019
conversion conversion n/a car top needs to be cleaned 7/25/2019
conversion conversion n/a all rags,oil,ect. needs to be removed from undervalves & pump and leaks repaired 7/25/2019
conversion conversion n/a jack needs to be repacked 7/25/2019
conversion conversion n/a Pit needs to be cleaned all oil and trash 7/25/2019
conversion conversion n/a play in upper guide shoe housing needs replaced 7/25/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x 1.6 telephone will not call out 8/12/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x G(1)/ 110.11h : Lower secondary hoistway door retainers (fire tabs) shall be installed and engage the sill by not less than 1/4” 12/24/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x B(11) / 1.6.1 : 2-way communication device shall work. (REINSPECTION within 30 days) 12/24/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x G(1) / 1.18.1: Car Door restrictor shall work. (REINSPECTION WITHIN 30 DAYS) 12/24/2020
MO Minimum : Elevators (I) - Pits (I)1 I-1 PIT NEEDS TO BE DRY AND CLEAN OF ALL DEBREE---PIT BLANKETS (2nd year violation) 12/24/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 2018-2020 O(4) Cylinder packing must be replaced. REINSPECTION WITHIN 30 DAYS 12/24/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 2018-2020 O(4) Cylinder packing must be replaced. REINSPECTION WITHIN 30 DAYS 8/25/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x B(11)/1.6.1/8.11.2.1.1(f)/8.6.4.15 : 2-way communication device shall work and give proper location (REINSPECTION REQUIRED 12/6/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x B(11)/1.6.1/8.11.2.1.1(f)/8.6.4.15 : 2-way communication device shall work and give proper location (REINSPECTION REQUIRED) 12/6/2021
MO Minimum : Elevators (H) - Machine Rooms (H)7 Repair/Replace faulty machine room GFCI 1/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Repair Pump/valve/oil cooler leaks, reinstall pump covers 1/14/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 H(2) / 101.3d(1)(b) Machine room door shall be self-closing and self-locking. Door currently is propped open for ventilation. 1/14/2022
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be dry and clean 1/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.4.8 clean oil from under pump unit 1/14/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate needs current certificate posted 1/14/2022
MO Minimum : Elevators (I) - Pits (I)1 I-1 PIT NEEDS TO BE DRY AND CLEAN OF ALL DEBREE---PIT BLANKETS (2nd year violation) 1/14/2022
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 2018-2020 O(4) Cylinder packing must be replaced. REINSPECTION WITHIN 30 DAYS 1/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements G-1 8.6.4.8 OIL NEEDS TO BE CLEANED OUT FROM UNDER PUMP UNIT ( multi-year violation) 1/14/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. 1/14/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces 8.6.4.8 clean oil from under pump unit. Pump/Valve/Oil Cooler assembly has multiple leaks, shall be properly repaired. (Multi year violation) 5/4/2023
MO Minimum : Elevators (I) - Pits (I)1 I(1) : Pit shall be kept clean. Remove excess debris, oil and oil pads, 5/4/2023
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.8 x In-Ground jack appears to be of single bottom design, based on head style and install year. Provide documentation to contrary, apply for variance to install Piston Gripper, or replace Jack. 5/4/2023
MO Minimum : Elevators (I) - Pits (I)1 Remove dirt and rubbish from pit floor 8/9/2024