Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room shall not be used for storage. Remove all non elevator related materials
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency battery lowering device is not working, needs repaired. Re-inspection required 12/12/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) x Emergency battery lowering device is not working, needs repaired. Re-inspection required
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not dial out therefore, it does not work on emergency power or normal power. Repair or replace 2.27.1.1.1 8/15/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform testing of OSV to complete inspection. Re-inspection required 12/12/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room