Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide a code compliant MCP including onsite documents. No maintenance charts. No monthly Fire Service checklist. No repair or test logs.
conversion conversion conversion - red tag x x The doors will not open at the recall floor on Phase 1 fire recall. Unit Red-Tagged. 8/23/2018
conversion conversion conversion - reinspect x Car door pressure exceeds the 30 lbs limit. 8/23/2018
MO Minimum : Elevators (H) - Machine Rooms (H)2 Walk in pit door shall be self-closing and self-locking. - Reinspection Required 10/1/2019
conversion conversion n/a Walk in pit door shall be self-closing and self-locking. 10/1/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant maintenance control program (MCP) shall be available and the documentation required to be kept on site, shall be located in the machine room. 10/7/2020
MO Minimum : Elevators (H) - Machine Rooms (H)8 A junction box for one of the machine room light fixtures is missing a cover. 10/7/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x The smoke detectors in the elevator lobbies shall be connected to the elevators and tested for proper operation. Unit left in service and local fire department notified of the situation. Violation corrected 9/28/2020 and scheduled for re-inspection on 10/9/2020. 10/9/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/3/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 11/3/2021