MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A code compliant maintenance control program (MCP) shall be available and the documentation required to be kept on site, shall be located in the machine room.
|
10/7/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
11/3/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be displayed in the elevator machine room.
|
11/3/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
A junction box for one of the machine room light fixtures is missing a cover.
|
10/7/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Car door pressure exceeds the 30 lbs limit.
|
8/23/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide a code compliant MCP including onsite documents. No maintenance charts. No monthly Fire Service checklist. No repair or test logs.
|
|
conversion
|
conversion
|
conversion - red tag
|
x
|
x
|
The doors will not open at the recall floor on Phase 1 fire recall. Unit Red-Tagged.
|
8/23/2018
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
The smoke detectors in the elevator lobbies shall be connected to the elevators and tested for proper operation. Unit left in service and local fire department notified of the situation. Violation corrected 9/28/2020 and scheduled for re-inspection on 10/9/2020.
|
10/9/2020
|
conversion
|
conversion
|
n/a
|
|
|
Walk in pit door shall be self-closing and self-locking.
|
10/1/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Walk in pit door shall be self-closing and self-locking. - Reinspection Required
|
10/1/2019
|