MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
Need to replace all open wiring on car top with NFPA 70 code compliant wiring. Re-inspection required
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)9 Capacity Plate
|
|
|
Need to post capacity inside the elevator cab
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide a code compliant MCP including onsite documents. No maintenance charts. No Monthly Fire service checklist. No repair or test logs.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A code compliant maintenance control program (MCP) shall be available and the documentation required to be kept on site, shall be located in the machine room.
|
10/7/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
11/3/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
The smoke detectors in the elevator lobbies shall be connected to the elevators and tested for proper operation. Unit left in service and local fire department notified of the situation. Violation corrected 9/28/2020 and scheduled for re-inspection on 10/9/2020.
|
10/9/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Phase 2 fire service does not work.
|
8/23/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Still need to test counterweight buffer.
|
8/23/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Still need to test fire service.
|
8/23/2018
|
conversion
|
conversion
|
n/a
|
|
|
Recommend fall protection railing on top of car.
|
10/1/2019
|
conversion
|
conversion
|
n/a
|
|
|
Car top light shall work and shall be guarded.
|
10/1/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Phase 2 fire service does not work.
|
8/23/2018
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be displayed in the elevator machine room.
|
11/3/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|