Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Recommend fall protection railing on top of car. 10/1/2019
conversion conversion n/a Car top light shall work and shall be guarded. 10/1/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant maintenance control program (MCP) shall be available and the documentation required to be kept on site, shall be located in the machine room. 10/7/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/3/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 11/3/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide a code compliant MCP including onsite documents. No maintenance charts. No Monthly Fire service checklist. No repair or test logs.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)9 Capacity Plate Need to post capacity inside the elevator cab
MO Minimum : Elevators (A) - Hoistways (A)16 Need to replace all open wiring on car top with NFPA 70 code compliant wiring. Re-inspection required
MO Minimum : Elevators (S) - Fire Service (S)1 x x The smoke detectors in the elevator lobbies shall be connected to the elevators and tested for proper operation. Unit left in service and local fire department notified of the situation. Violation corrected 9/28/2020 and scheduled for re-inspection on 10/9/2020. 10/9/2020
conversion conversion conversion - reinspect x Still need to test counterweight buffer. 8/23/2018
conversion conversion conversion - reinspect x Still need to test fire service. 8/23/2018
conversion conversion conversion - reinspect x Phase 2 fire service does not work. 8/23/2018
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 2 fire service does not work. 8/23/2018