Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Two-way communication device is not functioning.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 6/1/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing of smokes, heats, and shunt trip must be completed. 4/24/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The means of egress at the alternate fire service floor shall not be blocked by a locked door. Note: Currently the alternate fire service floor is a locked lobby with no escape for passengers. The door shall unlock automatically in the case of fire. 4/24/2024
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 2.29.1 x Both door jambs of every elevator entrance at the designated level and alternate level shall be marked with a unique identification with a minimum of 2 inches in height and of contrasting color to its background. 4/24/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x 2.1.6.1 - The overhead fasteners protruding through the ceiling shall be cut off flush to prevent a hazardous situation. 4/24/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.