MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The means of egress at the alternate fire service floor shall not be blocked by a locked door. Note: Currently the alternate fire service floor is a locked lobby with no escape for passengers. The door shall unlock automatically in the case of fire.
|
4/24/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing of smokes, heats, and shunt trip must be completed.
|
4/24/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device is not functioning.
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
2.1.6.1 - The overhead fasteners protruding through the ceiling shall be cut off flush to prevent a hazardous situation.
|
4/24/2024
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
2.29.1
|
x
|
|
Both door jambs of every elevator entrance at the designated level and alternate level shall be marked with a unique identification with a minimum of 2 inches in height and of contrasting color to its background.
|
4/24/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
6/1/2021
|