Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current state operating certificate shall be displayed in the machine room in a noncombustible frame.
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No Machine room does not close completely and latch.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit lighting shall work
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Car top shall be free of oil and debris.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency lighting shall work.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Repair inoperable emergency phone. 4/17/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working. 3/1/2021
MO Minimum : Elevators (D) - Brakes (D)1 Yes Yes Car brake failed to hold 125% - red tagged 4/15/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Incomplete test - check fire service, buffer, safeties, slide, phone/lights/alarm bell. 4/15/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit No No Clean car top and pit. 2/6/2026
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Elevator pit light shall work with a minimum of 5 foot candles. 2/6/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Elevator pit shall be clean of all debris 2/6/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Elevator car top shall remain clean to prevent any hazards 2/6/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work on 110v emergency power or normal power. Repair or replace 8/13/2026