Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Clean car top and pit.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Elevator pit light shall work with a minimum of 5 foot candles.
MO Minimum : Elevators (I) - Pits (I)1 Elevator pit shall be clean of all debris
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Elevator car top shall remain clean to prevent any hazards
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work on 110v emergency power or normal power. Repair or replace
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Repair inoperable emergency phone. 4/17/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone not working. 3/1/2021
MO Minimum : Elevators (D) - Brakes (D)1 x x Car brake failed to hold 125% - red tagged 4/15/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Incomplete test - check fire service, buffer, safeties, slide, phone/lights/alarm bell. 4/15/2022