Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x emergency phone did not work, provide working phone line 3/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Could not get the intercom to work that is being used as an emergency phone, need to have instructions on how to operate the intercom posted on the inside of the phone cabinet door 2/25/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate state operating certificate in the machine room is to be updated annually, the one that is on display in the machine room is from 2009
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x repair the fire service phase 1 audible signal, the tone device is barely audible 2/28/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate display a copy of the state operating certificate in the machine room
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 car top inspection station stop switch is broken internally, replace stop switch
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Car top inspection station stop switch is broken internally, replace stop switch, had to jump out stop switch in the inspection station