Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 OSV is not sealed and must have a cat 5 weight test performed within 90 days or less 10/21/2021
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) There needs to be a maintenance control program on site 4/19/2022
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Fire extinguisher is expired, have serviced or replaced 9/14/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light still does not work 1/25/2022