Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The annual inspection was not completed. The following items shall be tested: Relief pressure, pressure switch, low oil timer. 8/4/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 11/13/2019
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 1001.2(b)(11) The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. 11/22/2022
A17.1-1996 : Elevators 3.5 - Normal terminal stopping device 1002.2e x Car shall stop in the down direction while on car top inspection prior to striking the buffer. When the car strikes the buffer, it activates the low pressure switch, rendering the car inoperable. 11/13/2019
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. 2/14/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall work. Take corrective action as needed. 8/28/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 The MCP, including PM records and monthly fire service test log are not being properly documented. 2/14/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/22/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 11/22/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 11/22/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) x A category 5 full load test shall be performed on the overspeed valve in 2022. 9/2/2022