Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 6/4/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) Yes Yes Elevator failed to respond, return to alternate floor during machine room smoke detector simulation. Repair 5/4/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 3.2 Yes No Pit shall have 10 ft candles of illumination 5/20/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 1/22/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Provide existing phone to work. 1/22/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate. 1/22/2026
A17.1-1996 : Elevators 2.4 - Machine space 1001.2(b)(4) No No Ceiling tiles should have a fire rating. 1/22/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Remove scavenger pump and provide containment bucket in pit. 1/22/2026