Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.4 - Machine space 1001.2(b)(4) Ceiling tiles should have a fire rating.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Remove scavenger pump and provide containment bucket in pit.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 6/4/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) x x Elevator failed to respond, return to alternate floor during machine room smoke detector simulation. Repair 5/4/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 3.2 x Pit shall have 10 ft candles of illumination 5/20/2022