Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Sheave seal worn and leaking, repair as needed. Clean up oil.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Hoistway door closer is missing retainer clip for rod, replace.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Smoke detector in pit has been removed, determine cause. Replace.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Heat detector head in pit has been removed. Determine cause, replace.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 2/25/2021
A17.1-1996 : Elevators 2.15 - Static control 1001.2(b)(13) x Elevator failed static 125% test. Brake did not hold. Elevator red-tagged. 10/29/2018
A17.1-1996 : Elevators 2.18 - Traction drive machines 1001.2(b)(16) x Drive sheave seals and worm shaft seals are worn and leaking. Repair as needed. 11/15/2021
A17.1-1996 : Elevators 2.19 - Gears, bearings, and flexible couplings 1001.2(b)(17) - no reinspect Worm shaft seal on drive machine worn and leaking. Repair/replace as needed. 2/11/2021
A17.1-1996 : Elevators 2.19 - Gears, bearings, and flexible couplings 1001.2(b)(17) - no reinspect Worm gear is leaking excessively on car top and in the cab. 2/13/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on-site maintenance control program. 11/15/2021
A17.1-1996 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 1206.2(c) Clean oil from car top, fan and ceiling/fixtures. 11/15/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Clean pit. 11/15/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x Water in the pit. 5/13/2020
conversion conversion n/a Maintain machine room lighting three out of four bulbs out 2/13/2020
conversion conversion n/a Pit light inopeartive 2/13/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 2/13/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate. 2/11/2021