A17.1-1996 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
1206.2(c)
|
|
|
Clean oil from car top, fan and ceiling/fixtures.
|
11/15/2021
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Clean pit.
|
11/15/2021
|
A17.1-1996 : Elevators
|
2.18 - Traction drive machines
|
1001.2(b)(16)
|
x
|
|
Drive sheave seals and worm shaft seals are worn and leaking. Repair as needed.
|
11/15/2021
|
A17.1-1996 : Elevators
|
2.15 - Static control
|
1001.2(b)(13)
|
|
x
|
Elevator failed static 125% test. Brake did not hold. Elevator red-tagged.
|
10/29/2018
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
2/25/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Heat detector head in pit has been removed. Determine cause, replace.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Hoistway door closer is missing retainer clip for rod, replace.
|
|
conversion
|
conversion
|
n/a
|
|
|
Maintain machine room lighting three out of four bulbs out
|
2/13/2020
|
conversion
|
conversion
|
n/a
|
|
|
Pit light inopeartive
|
2/13/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
2/13/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate.
|
2/11/2021
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide on-site maintenance control program.
|
11/15/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Sheave seal worn and leaking, repair as needed. Clean up oil.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Smoke detector in pit has been removed, determine cause. Replace.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
Water in the pit.
|
5/13/2020
|
A17.1-1996 : Elevators
|
2.19 - Gears, bearings, and flexible couplings
|
1001.2(b)(17) - no reinspect
|
|
|
Worm gear is leaking excessively on car top and in the cab.
|
2/13/2020
|
A17.1-1996 : Elevators
|
2.19 - Gears, bearings, and flexible couplings
|
1001.2(b)(17) - no reinspect
|
|
|
Worm shaft seal on drive machine worn and leaking. Repair/replace as needed.
|
2/11/2021
|