conversion
|
conversion
|
n/a
|
|
|
The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
The firemen's emergency service phase I and II operations were tested and the following deficiencies were noted:In phase II operation, the car door open sequence is not constant pressure.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
The firemen's emergency service phase I and II operations were tested and the following deficiencies were noted:In phase II operation, the elevator car will not stay in position without the car doors open.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
The firemen's emergency service phase I and II operations were tested and the following deficiencies were noted:The ?Call Cancel? operation did not work in phase II as required. When the ?Call Cancel? is initiated the car continues to move to the top of the hoistway. The car is required to stop at the nearest floor.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
The firemen's emergency service phase I and II operations were tested and the following deficiencies were noted:The audible signal device did not sound when phase I was activated.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
The firemen's emergency service phase I and II operations were tested and the following deficiencies were noted:The fireman service operation light jewel doesn?t work in the car.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
The firemen's emergency service phase I and II operations were tested and the following deficiencies were noted:The fireman service phase I operation doesn?t work as required. There are no smoke detectors tied into the elevator controller to initiate phase I fireman service. Recommend the elevator maintenance company and the alarm companies initiate these devices together and retest the system.
|
|