Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light battery is dead and needs to be replaced 7/27/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone line is dead, provide a working phone line to the elevator controller 7/27/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x the phone line for the emergency phone did not work, provide a working phone line 7/26/2023
A17.1-1996 : Elevators 3.3 - Top-of-car operating device 210.1d the top of car operating device, would not run in the down direction on car top inspection 7/26/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x the backup battery for the emergency phone is not working, phone will not call out when the 110 volt power is off 10/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation perform a monthly fire service test and fill out the log in the machine room 6/14/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) monthly fire service test log is to be kept in the machine room 6/14/2024
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation provide maintenance control program on site documents 6/14/2024
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.3.1.2(j) Machine room fire extinguisher last checked in 2019 6/14/2024
A17.1-2016 : Elevators 1.4 - Sills and car floor 8.11.3.1.1(d) repair the grout in the bottom landing sill, it is crumbling and a trip hazard 6/14/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers inspection tag on the fire extinguisher in the machine room is from 2019, have the fire extinguisher inspected and tagged annually 6/14/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate the copy of the state operating certificate in the machine room is from 2017, post a new copy of the state certificeate in the machine room annually when received from the state 6/14/2024
A17.1-1996 : Elevators 1.4 - Sills and car floor 110.11a the bottom landing hoistway door sill has not been grouted, there is a gap between the concrete floor and the hoistway door sill 6/14/2024