Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The emergency power and fireman’s service operation shall be tested before the inspection is completed.
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in dust and debris. The pit shall be cleaned.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel.
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller.
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller.
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 201 x The car buffer switch failed to return after activation and had to be manually reset. Repair or replace switch to reset automatically when the buffer returns after activation. Reinspection is required. 9/12/2022
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 201 x The car buffer switch failed to return after activation and had to be manually reset. Repair or replace switch to reset automatically when the buffer returns after activation. Reinspection is required. 6/4/2024
A17.1-1996 : Elevators 3.28 - Counterweight and counterweight buffer 202 There is a bottom guide roller on the counterweight that has deteriorated and shall be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The emergency phone door is missing in the elevator cab and shall be reinstalled to allow access for passenger’s and emergency personnel