Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting A number of machine room lighting fixtures were not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel.
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri.
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in dust and debris. The pit shall be cleaned.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Elevator machine room has multiple light bulbs that do not work, needs repaired
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in dust and debris. The pit shall be cleaned.
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 201 x The car buffer switch failed to return after activation and had to be manually reset. Repair or replace switch to reset automatically when the buffer returns after activation. Reinspection is required. 9/12/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The emergency power and fireman’s service operation shall be tested before the inspection is completed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Elevator cab emergency lights do not work, need repaired. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The emergency power and fireman’s service operation shall be tested before the inspection is completed. 7/7/2025
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Need to test elevator on phase I & II fire service. Re-inspection required
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 201 x The counterweight buffer switch failed to return after activation and had to be manually reset. Repair or replace switch to reset automatically when the buffer returns after activation. Reinspection is required. 7/7/2025