Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(a) Elevators Placed in Inactive Status Yes Yes Elevator has been shut off at the disconnect. Elevator does not run and has not had an inspection since 6/13/22. Either apply for the elevator to be placed in inactive status for a maximum of 2 years, repair elevator and perform Cat 5 full load test or de-commission elevator.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light and switch are required. 5/26/2026
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light and switch are required. 5/26/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)5 No No Rear car door gate switch needs to be adjusted. 5/26/2026
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light and switch required. 5/26/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room light shall work. 5/26/2026
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Install a permanent light & receptacle in pit with switch accessible from bottom hall door 5/26/2026