MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Doors do not open on Phase 2. Unit red tagged.
|
6/22/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
6/22/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Install pit light with switch accessible from landing.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Install pit light with switch accessible from landing.
|
|
conversion
|
conversion
|
n/a
|
|
|
Phase II sign in car
|
11/12/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
Pit is 4 ft deep, needs pit ladder. Pit ladder needs to extend 30" above bottom floor entrance
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit needs a permanent light & receptacle with light switch accessible from the bottom floor door
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Return to Phase I off of phase II not working
|