Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service (S)1 x x Doors do not open on Phase 2. Unit red tagged. 6/22/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 6/22/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Install pit light with switch accessible from landing.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Install pit light with switch accessible from landing.
conversion conversion n/a Phase II sign in car 11/12/2019
MO Minimum : Elevators (I) - Pits (I)5 Pit is 4 ft deep, needs pit ladder. Pit ladder needs to extend 30" above bottom floor entrance
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit needs a permanent light & receptacle with light switch accessible from the bottom floor door
conversion conversion conversion - reinspect x Return to Phase I off of phase II not working 6/14/2019